What are the maximum allowable temperature requirements for various wires and cables?
1. PVC insulated wire and cable models: BV, BVR, BVV, RV, RVV, VV, VLV, etc.
Temperature requirements
(1)Operating temperature: The maximum rated operating temperature of the cable conductor is 70°C.
(2)Laying temperature: The cable laying temperature shall not be lower than 0℃.
2. Cross-linked polyethylene insulated cable models: YJV, YJLV, YJV22, YJLV22, YJV23, YJLV23
Temperature requirements
(1)Operating temperature: The maximum rated operating temperature of the cable conductor is 90°C.
(2)Overload temperature: The maximum temperature of the cable for short-term overload shall not exceed 130°C.
(3)Short-circuit temperature: When the cable is short-circuited, the maximum temperature shall not exceed 250°C. (The maximum duration does not exceed 5 seconds).
(4)Laying temperature: The cable laying temperature shall not be lower than 0℃. Preheating is required when applying below 0℃.
3. Overhead insulated cable models: JKY, JKLY, JKYJ, JKLYJ, etc.
Temperature requirements
(1)The long-term allowable operating temperature of the cable is 90°C for cross-linked polyethylene insulation and 75°C for high-density polyethylene insulation.
(2)When short-circuited (the most extended duration does not exceed 5 seconds), the maximum temperature of the cable is 150°C for high-density polyethylene insulation and 250°C for cross-linked polyethylene insulation.
(3)The laying temperature of the cable should not be lower than -20℃.
4. Prefabricated branch cable models: FZ-VV, FZ-YJV, FZ-WDZ-YJY, etc.
Temperature requirements
(1)The long-term allowable operating temperature of cables: PVC insulation is 70°C; cross-linked polyethylene insulation is 90°C.
(2)When the cable is short-circuited (the most extended duration does not exceed 5 seconds), the maximum temperature of the line: PVC insulation is 160°C; cross-linked polyethylene insulation is 250°C.
(3)The laying temperature of cables should not be lower than 0℃.
5. Rubber sheathed cable models: YZ, YC, YZW, YCW.
Temperature requirements
(1)Working temperature: The maximum rated operating temperature of the cable conductor does not exceed 70°C.
6. Welding machine cable models: YHZ, YH
Temperature requirements
(1)Working temperature: The maximum rated operating temperature of the cable conductor does not exceed 70°C.
7. Coaxial cable model: SYWV
Temperature requirements
(1)Ambient temperature: PVC sheath is -25~+70℃, polyethylene sheath is -40~+70℃.